Flame detection
SharpEye Flame detectors 40/40
About SharpEye 40/40 series
SharpEye 40/40I - Triple IR (IR3) Flame Detector
SharpEye 40/40M - Multi IR Flame Detector
SharpEye 40/40L-LB; L4-L4B - UV/IR Flame Detector
SharpEye 40/40U-UB - UV Flame Detector
SharpEye 40/40R - Single IR Flame Detector
SharpEye Flame detectors 20/20
SharpEye Mini Flame detectors 20/20
Control Panels
Accessoiries
Approvals
Library

SharpEye 40/40L-LB; L4-L4B - UV/IR Flame Detector

We offer two versions of the new SharpEye 40/40 Series UV/IR Flame Detectors:

Model SharpEye 40/40L (& LB) provides a combination of UV and IR sensors, where the IR sensor operates at a wavelength of 2.5-3.0 µm, and can detect hydrocarbon-based fuel and gas fires, hydroxyl and hydrogen fires, as well as metal and inorganic fires.

Model SharpEye 40/40L4 (& L4B) is identical to the 40/40L except that the IR sensor works at a wavelength of 4.5 µm and is only suitable for hydrocarbon-based fires. The UV/IR flame detector senses radiant energy in the short wave section of both the ultraviolet and infrared portions of the electromagnetic spectrum. The signals from both sensors are analyzed for frequency, intensity and duration. Simultaneous detection of radiant energy in both the UV and IR sensors triggers an alarm signal.

The UV sensor incorporates a special logic circuit that helps prevent false alarms caused by solar radiation

Features:

- UV/IR Dual-Sensor
- High-Speed Response - 150 msec Response to Saturated Signal Solar blind
- Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
- Heated window for operation in harsh weather conditions (snow, ice, condensation)
- Multiple output options for maximum flexibility and compatibility

- Relays (3) for Alarm, Fault and Auxiliary
- 0-20mA (stepped)
- HART Protocol for maintenance and asset management
- RS-485, Modbus Compatible

- High Reliability - MTBF - minimum 150,000 hours
- 5-Year Warranty
- User Programmable via HART or RS-485  

REGISTERED USER

40/40L-LB; L4-L4B APPROVALS

Hazardous Area Ex Approvals

  • ATEX and IECEx
  • FM / CSA 

Performance Approvals

  • EN54-10 (LPCB) 
  • FM-3260 (FM)

Reliability Approvals

  • IEC61508 - SIL2 (TUV)  

40/40L-LB; L4-L4B DOCUMENTATION


Provided document(s) are PDF files which are opened with Acrobat Reader. 

If you dont have this program, a free download is available HERE.